Serial Easy9 Pro
Product or component type leakage current circuit cutter (RCCB)
Product Group Easy9 Pro RCCB
Device Application Distribution
POOL DESCRIPTION 4P
neutral location left
[In] Nominal Current 40 A
Network Type AC
soil leak sensitivity 30 mA
Soil leakage protection time delay instant
soil leakage protection class AC type
hominal cutting and closing capacity 500 A
Nominal conditional short circuit current 10 ka
The location of the device in the system
Network Frequency 50/60 Hz
[UE] Nominal Working Voltage 415 V AC 50/60 Hz
Residual current opening technology voltage independent
[Ui] Nominal Insulation Voltage 500 V
[UIMP] Nominal impact resistance voltage 4 kV
contact location indicator yes
DUTTING FLOOR 250 A
Control Type
Assembly type can be installed
Assembly support DIN RAYA
Comb Busbar Distribution Bloc Compatibility Top: Pin Type
Alt: Pin/Fork Type
9 mm screw step 8
Height 85 mm
Width 72 mm
Depth 79 mm
Product weight 354 g
Color Gray (Ral 7035)
Mechanical durability 5000 Cycles
Electric strength 4000 Cycles
Connections – Terminals Tunnel Type Terminal (Top and Bottom) 1… 35 mm² hard
Tunnel Type Terminal (Top and Bottom) 1… 25 mm² flexible