LC1D65ED
Schneider Electric TeSys Deca Advanced contactor, TeSys Deca,3P(3NO),AC-3/AC-3e 440V 65A,coil 36V DC, screw clamp terminals.
إظهار المواصفات
Main Characteristics
| Lifecycle status | Discontinued by the manufacturer |
|---|---|
| Range | TeSys |
| Range of Product | TeSys Deca Advanced |
| Product or Component Type | Contactor |
| Contactor application | Resistive load |
| Utilisation category | AC-3; AC-3e; AC-1; AC-4 |
| Poles description | 3P |
| [Ue] rated operational voltage | Power circuit <= 690 V AC 25...400 Hz |
| [Ie] rated operational current | 65 A (at <140 °F (60 °C)) at <= 440 V AC AC-3 for power circuit; 65 A (at <140 °F (60 °C)) at <= 440 V AC AC-3e for power circuit; 80 A (at <140 °F (60 °C)) at <= 440 V AC AC-1 for power circuit |
| [Uc] control circuit voltage | 48 V DC |
Technical Data
| Motor power kW | 18.5 kW at 220/230 V AC 50/60 Hz (AC-3); 30 kW at 380/400 V AC 50/60 Hz (AC-3); 30 kW at 415 V AC 50/60 Hz (AC-3); 30 kW at 440 V AC 50/60 Hz (AC-3); 37 kW at 500 V AC 50/60 Hz (AC-3); 37 kW at 660/690 V AC 50/60 Hz (AC-3); 37 kW at 1000 V AC 50/60 Hz (AC-3); 18.5 kW at 220/230 V AC 50/60 Hz (AC-3e); 30 kW at 380/400 V AC 50/60 Hz (AC-3e); 30 kW at 415 V AC 50/60 Hz (AC-3e); 30 kW at 440 V AC 50/60 Hz (AC-3e); 37 kW at 500 V AC 50/60 Hz (AC-3e); 37 kW at 660/690 V AC 50/60 Hz (AC-3e); 37 kW at 1000 V AC 50/60 Hz (AC-3e); 11 kW at 400 V AC 50/60 Hz (AC-4) |
|---|---|
| Maximum Horse Power Rating | 10 hp at 230/240 V AC 60 Hz for 1 phase motors; 20 hp at 200/208 V AC 60 Hz for 3 phase motors; 20 hp at 230/240 V AC 60 Hz for 3 phase motors; 40 hp at 460/480 V AC 60 Hz for 3 phase motors; 50 hp at 575/600 V AC 60 Hz for 3 phase motors; 5 hp at 115 V AC 60 Hz for 1 phase motors |
| Compatibility code | LC1D |
| Pole contact composition | 3 NO |
| Protective cover | With |
| [Ith] conventional free air thermal current | 80 A (at 140 °F (60 °C)) for power circuit; 10 A (at 140 °F (60 °C)) for control circuit |
| Irms rated making capacity | 1000 A at 440 V DC for power circuit conforming to IEC 60947; 1000 A at 440 V for power circuit conforming to IEC 60947; 250 A DC for control circuit conforming to IEC 60947-5-1 |
| Rated breaking capacity | 1000 A at 440 V for power circuit conforming to IEC 60947 |
| Associated fuse rating | 125 A gG at <= 690 V coordination type 2 for power circuit; 160 A gG at <= 690 V coordination type 1 for power circuit conforming to IEC 60947-5-1; 125 A gG at <= 690 V coordination type 1 for power circuit; 10 A gG for control circuit conforming to IEC 60947-5-1 |
| Power dissipation per pole | 6.4 W AC-1; 4.2 W AC-3e; 4.2 W AC-3 |
| [Ui] rated insulation voltage | Control circuit 600 V UL; Power circuit 600 V CSA; Power circuit 600 V UL IEC 60947-1; Control circuit 690 V IEC 60947-1; Power circuit 690 V IEC 60947-1; Power circuit 1000 V CSA IEC 60947-4-1; Control circuit 600 V CSA |
| Overvoltage category | III |
| [Uimp] rated impulse withstand voltage | 8 kV IEC 60947 |
| Safety reliability level | B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1; B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 |
| Mechanical durability | 10 Mcycles |
| Control circuit type | DC wide range |
| Coil technology | Built-in bidirectional peak limiting diode suppressor |
| Control circuit voltage limits | 0.75...1.25 Uc (-40…140 °F (-40…60 °C)):operational DC; 1...1.25 Uc (140…158 °F (60…70 °C)):operational DC; 0.1...0.3 Uc (-40…158 °F (-40…70 °C)):drop-out DC |
| Inrush power in W | 19 W 68 °F (20 °C)) |
| Hold-in power consumption in W | 22 W 68 °F (20 °C) |
| Rated operational power in W | 38 W 48 V DC-13 3000000 cycles - control circuit; 76 W 48 V DC-13 1000000 cycles - control circuit; 12 W 48 V DC-13 10000000 cycles - control circuit |
| Operating time | 50 ±15 % ms closing; 20 ±20 % ms opening |
| Time constant | 34 ms |
| Maximum operating rate | 3600 cyc/h at 60 °C |
| Connections - terminals | Control circuit: screw clamp terminals 2 0.002…0.006 in² (1…4 mm²) - cable stiffness: rigid without cable end; Control circuit: screw clamp terminals 1 0.002…0.006 in² (1…4 mm²) - cable stiffness: flexible without cable end; Control circuit: screw clamp terminals 2 0.002…0.006 in² (1…4 mm²) - cable stiffness: flexible without cable end; Control circuit: screw clamp terminals 1 0.002…0.004 in² (1…2.5 mm²) - cable stiffness: flexible with cable end; Control circuit: screw clamp terminals 2 0.002…0.004 in² (1…2.5 mm²) - cable stiffness: flexible with cable end; Power circuit: screw clamp terminals 1 0.004…0.04 in² (2.5…25 mm²) - cable stiffness: rigid; Power circuit: screw clamp terminals 2 0.004…0.02 in² (2.5…16 mm²) - cable stiffness: rigid without cable end; Power circuit: screw clamp terminals 1 0.004…0.04 in² (2.5…25 mm²) - cable stiffness: flexible without cable end; Power circuit: screw clamp terminals 2 0.004…0.02 in² (2.5…16 mm²) - cable stiffness: flexible without cable end; Power circuit: screw clamp terminals 1 0.004…0.04 in² (2.5…25 mm²) - cable stiffness: flexible with cable end; Power circuit: screw clamp terminals 2 0.004…0.02 in² (2.5…10 mm²) - cable stiffness: flexible with cable end; Control circuit: screw clamp terminals 2 0.002…0.006 in² (1…4 mm²) - cable stiffness: rigid; Control circuit: screw clamp terminals 1 0.002…0.006 in² (1…4 mm²) - cable stiffness: rigid |
| Tightening torque | Control circuit 15.05 lbf.in (1.7 N.m) screw clamp terminal Philips No 2; Power circuit 44.3 lbf.in (5 N.m) screw terminal flat Ø 6 to Ø 8 mm; Control circuit 15.05 lbf.in (1.7 N.m) screw clamp terminal pozidriv No 2; Control circuit 15.05 lbf.in (1.7 N.m) screw clamp terminal flat Ø 6 mm |
| Auxiliary contact composition | 1 NO + 1 NC |
| Auxiliary contacts type | Mirror contact 1 NC IEC 60947-4-1; Mechanically linked 1 NO + 1 NC IEC 60947-5-1 |
| Minimum switching voltage | 17 V for control circuit |
| Minimum switching current | 5 mA for control circuit |
| Insulation resistance | > 10 MOhm for control circuit |
| Non-overlap time | 1.5 ms on energisation between NC and NO contacts; 1.5 ms on de-energisation between NC and NO contacts |
| Mounting Support | Plate |
Environment & Certifications
| Standards | UL 60947-4-1; EN 60947-5-1; EN 60947-4-1; IEC 60947-5-1; CSA C22.2 No 14; IEC 60947-4-1 |
|---|---|
| Product Certifications | CCC; CSA; GOST; RINA; GL; DNV; LROS (Lloyds register of shipping); UL; UKCA |
| IP degree of protection | IP2X VDE 0106; IP2X IEC 60529 |
| Climatic withstand | IACS E10 exposure to damp heat |
| Operating altitude | 0...9842.52 ft (0...3000 m) |
| Fire resistance | 1562 °F (850 °C) IEC 60695-2-1 |
| Flame retardance | V1 conforming to UL 94 |
| Mechanical robustness | Shocks contactor closed 15 Gn for 11 ms) ; Vibrations contactor opened 2 Gn, 5...300 Hz) ; Vibrations contactor closed 4 Gn, 5...300 Hz) ; Shocks contactor opened 10 Gn for 11 ms) |
| Height | 5 in (127 mm) |
| Width | 3.3 in (85 mm) |
| Depth | 6.9 in (176 mm) |
| Net Weight | 4.817 lb(US) (2.185 kg) |
Packaging & Logistics
| Nbr. of units in pkg. | 1 |
|---|---|
| Package 1 Height | 7.362 in (18.700 cm) |
| Package 1 Width | 5.591 in (14.200 cm) |
| Package 1 Length | 3.465 in (8.800 cm) |
| Package weight(Lbs) | 4.833 lb(US) (2.192 kg) |
| Number of Units in Package 2 | 2 |
| Package 2 Height | 5.9 in (15 cm) |
| Package 2 Width | 11.8 in (30 cm) |
| Package 2 Length | 15.7 in (40 cm) |
| Package 2 Weight | 10.238 lb(US) (4.644 kg) |
| Number of Units in Package 3 | 32 |
| Package 3 Height | 29.528 in (75.000 cm) |
| Package 3 Width | 31.496 in (80.000 cm) |
| Package 3 Length | 23.622 in (60.000 cm) |
| Package 3 Weight | 181.449 lb(US) (82.304 kg) |
| GTIN | 3389110436600 |
Warranty
| Warranty (in months) | 18 |
|---|
يتناسب جيدًا مع
تسليم موثوق للمنتجات الصناعية في جميع أنحاء العالم.
تجربة خالية من المخاطر لمدة 90 يومًا
ضمان لمدة سنتين
شحن وإرجاع مجانيان

LC1D65ED
إذا كانت لديك أي أسئلة، فنحن نرحب باتصالك بنا في أي وقت. سنرد عليك في أقرب وقت ممكن، خلال 24 ساعة في أيام الأسبوع.
-
معلومات الشحن
استخدم هذا النص للإجابة على الأسئلة بأكبر قدر ممكن من التفصيل لعملائك.
-
دعم العملاء
استخدم هذا النص للإجابة على الأسئلة بأكبر قدر ممكن من التفصيل لعملائك.
-
الأسئلة الشائعة
استخدم هذا النص للإجابة على الأسئلة بأكبر قدر ممكن من التفصيل لعملائك.
-
اتصل بنا
استخدم هذا النص للإجابة على الأسئلة بأكبر قدر ممكن من التفصيل لعملائك.
الأسئلة الشائعة
يرجى قراءة صفحة الأسئلة الشائعة لمعرفة المزيد.
هل تقومون بتوريد منتجات أصلية؟
نحن نوفر منتجات الأتمتة الصناعية والكهربائية الأصلية من الشركات المصنعة الرائدة بما في ذلك سيمنز (Siemens) وإيه بي بي (ABB) وشنايدر إليكتريك (Schneider Electric) وفينكس كونتاكت (Phoenix Contact) وإيتون (Eaton). أصالة المنتجات وجودتها هي أولويتنا.
هل يمكنني طلب عرض أسعار؟
نعم. إذا لم يتم عرض الأسعار أو كنت بحاجة إلى عناصر متعددة، فما عليك سوى استخدام زر "طلب عرض أسعار" أو الاتصال بفريق المبيعات لدينا للحصول على عرض أسعار مخصص.
هل تشحنون دوليًا؟
نعم. نحن نوفر خدمة الشحن إلى جميع أنحاء العالم، ويمكننا توصيل المنتجات إلى العملاء في جميع أنحاء أوروبا والشرق الأوسط وآسيا ووجهات دولية أخرى.
هل يمكنك توفير قطع غيار قديمة أو يصعب العثور عليها؟
نعم. نحن متخصصون في توريد مكونات الأتمتة الصناعية التي توقف إنتاجها أو عفا عليها الزمن أو يصعب العثور عليها من خلال شبكة الموردين العالمية لدينا.
ما هي الصناعات التي تخدمونها؟
نحن ندعم العملاء في قطاعات الصناعة والنفط والغاز والطاقة والمرافق ومعالجة المياه والبنية التحتية والأتمتة الصناعية.