REL72500
Schneider Electric Protection and control relay, PowerLogic P7, motor standard, 5CT, 4VT, 24BI, 20BO, 24-34V, ethernet RJ45.
إظهار المواصفات
Main Characteristics
| Range of Product | PowerLogic P7 |
|---|---|
| Product or Component Type | Protection and control relay |
| Relay application | Motor application and bay control |
| Product reference | P7 |
| Mounting case size | 40TE |
| Device mounting | Flush |
| Mounting Support | 19" rack |
| Mounting Mode | Flush mounting; Rack-mounted |
| Power supply | 24...34 V DC |
| Measuring inputs | 4 CT 1/5 A; 1 CT 1 A; 4 VT |
| Number of Digital Inputs (DI) | 24 |
| Number of analogue inputs | 8 RTD optional |
| Number of Digital Outputs (DO) | 20; 1 watchdog |
| Type of temperature module connection | 2 twisted, type A, shielded wires (RS485) |
| Communication ports | 1 CAN port; 1 Ethernet TCP/IP; 2 SFP ports; 1 USB port; 1 COM serial link |
| Communication protocols | Modbus serial and TCP; DNP3 serial and TCP; IEC 61850 Ed 2.1; IEC 61869-9; IEC 61850-9-2 LE |
| Redundancy communication port protocol | HSR; PRP; RSTP; Failover |
| Cybersecurity | IEC 62443 SL2; LDAP; RADIUS based user authentication; Port hardening; Role-based access control; Secure boot; Security log; Syslog protocol support; Secured communication with assciated tools; Password protection; Firmware signature; Client IP address filter; Pre-login banner; Security policy management |
| Protection functions | Phase overcurrent 50/51; Ground fault protection 50N/51N; Sensitive earth fault overcurrent 50G/51G; Negative sequence overcurrent 46; Inrush detection 68; Phase undercurrent 37; Undervoltage 27; Overvoltage 59; Positive sequence undervoltage 47; Overfrequency 81O; Underfrequency 81U; High impedance differential 64REF; Motor differential 87M; Thermal overload for machines 49; Temperature monitoring (8 or 16 RTDs) 38/49T; Startup motoring 48; Locked rotor 51LR; Motor restart inhibition 66; Voltage check 47; Overspeed 12; Underspeed (2 set points) 14; Field loss (underimpedance) 40; Underimpedance 21; Out of step 78PS; CT supervision 60; VT supervision 60FL; Breaker failure 50 BF; Programmable logic |
| Measurement functions | Current 3-phase; RMS current 3-phase; Current sequence; Current 1-phase; RMS current 1-phase; Voltage 3-phase; RMS voltage 3-phase; Voltage sequence; Voltage 1-phase; RMS voltage 1-phase; Power fundamental frequency; Power factor; Active power fundamental frequency; Apparent power fundamental frequency; Reactive power fundamental frequency; RMS active power minimum; RMS reactive power maximum; RMS apparent power maximum; Active power demand maximum; Active power demand minimum; Reactive power demand maximum; Reactive power demand minimum; Apparent power demand maximum; Apparent power demand minimum; RMS phase current demand maximum; RMS phase current demand minimum; Earth fault current external measurement |
| Control functions | Switchgear control and monitoring; Programmable switchgear interlocking; Local/remote control; Programmable logic; Remote control; Function keys |
| Controllable switchgear devices | 10 controlled objects |
| Number of setting groups | 8 |
| Monitoring functions | Circuit breaker monitoring; Switch monitoring; Relay self-monitoring; Trip circuit supervision 74; Event counters; Watchdog |
| Logs and records | Disturbance recording; Event recording; Fault recording; Operation log |
| Switchgear diagnosis type | CT/VT supervision 60; Auxiliary power supply monitoring; Cumulative breaking current; Number of operations; DC battery voltage monitoring |
| Connections - terminals | Screw type terminals (digital input/output); Ring terminal (analogue input) |
Technical Data
| Input power interruption | 50 ms |
|---|---|
| Maximum power consumption in W | 24 W typical |
| Operating threshold | 24 V DC |
| Time synchronisation protocol | IRIG-B; SNTP; IEEE 1588 |
| Software name | PowerLogic Engineering Suite |
| Display type | Colour touchscreen 800 x 640 pixels |
| Display size | 7 inch |
| Information Displayed | Single line diagram; Menu-driven user interface |
| Control Button Type | 1 home physical key; 1 reset physical key; 12 customizable virtual function keys |
| Local signalling | 4 LEDs red/orange device status; 24 LEDs tri-colour programmable |
| Communication compatibility | DNP3; Modbus; IEC 61850 Ed 2.1 |
| Device connection | Connection to a PC USB; Extension port extension cable; Ethernet port RJ45; Serial port RS485 cable; SFP redundant Ethernet port fibre optic/RJ45 multi/single mode optional |
| Product Certifications | cUL Listed; UKCA; KETOP; CE; DNV |
| Height | 7.008 in (178 mm) |
| Width | 8.08 in (205.2 mm) |
| Depth | 11.1 in (282 mm) |
| Net weight | 19.4 lb(US) (8.8 kg) maximum |
Environment & Certifications
| Climatic withstand | Exposure to cold Ae IEC 60068-2-1; Exposure to dry heat Be IEC 60068-2-2; Exposure to damp heat in service Cab IEC 60068-2-78; Temperature variation Nb IEC 60068-2-14; Exposure to damp heat not in service Cab IEC 60068-2-30; Salt mist Kb/1 IEC 60068-2-52; Influence of corrosion/gas test 2 Ke IEC 60068-2-60; Influence of corrosion/gas test 4 Ke IEC 60068-2-60 |
|---|---|
| Mechanical robustness | Vibrations class 2) IEC 60255-21-1; Shocks class 2) IEC 60255-21-2; Shocks class 1) IEC 60255-21-2; Bumps class 1) IEC 60255-21-2; Seismic tests class 2) IEC 60255-21-3 |
| Electromagnetic compatibility | Electromagnetic immunity class A CISPR 11; Electromagnetic immunity class A CISPR 22; Electromagnetic immunity level 3 IEC 6100-4-3; Radiated radio-frequency electromagnetic field immunity test ANSI C37.90.2; Electrostatic discharge level 4 IEC 6100-4-2; Electrostatic discharge ANSI C37.90.3; Immunity to magnetic fields level 4 IEC 61000-4-8; Immunity to magnetic fields level 5 IEC 61000-4-9; Immunity to magnetic fields level 5 IEC 61000-4-10; Conducted RF disturbances level 3 IEC 61000-4-6; Fast transient bursts level 4 IEC 61000-4-4; Damped oscillatory wave level 3 IEC 61000-4-18; Damped oscillatory wave ANSI C37.90.1; Damped oscillatory wave level 3 IEC 61000-4-12; Conducted disturbance emission A IEC 61000-4-16; Surges level 4 IEC 61000-4-5 |
| Ambient air temperature for operation | -40…158 °F (-40…70 °C) 96 h ) |
| Ambient air temperature for storage | -40…185 °F (-40…85 °C) (96 h) |
| IP degree of protection | IP54 front IEC 60529; IP30 case IEC 60529; IP20 rear IEC 60529 |
| IK degree of protection | IK07 conforming to IEC 62262 |
| Maximum operating altitude | 6561.68 ft (2000 m) |
| Protective treatment | Conformal coating conforming to IEC 60068-2-52:Kb/1; Conformal coating conforming to IEC 60068-2-60:Ke |
| Relative humidity | 0…93 % at 104 °F (40 °C), without condensation, 56 days |
Packaging & Logistics
| Nbr. of units in pkg. | 1 |
|---|---|
| Package 1 Height | 11.8 in (30 cm) |
| Package 1 Width | 11.8 in (30 cm) |
| Package 1 Length | 15.7 in (40 cm) |
| Package weight(Lbs) | 18.115 lb(US) (8.217 kg) |
| GTIN | 3606486926505 |
| Country of origin | LV |
Warranty
| Warranty (in months) | 24 |
|---|
يتناسب جيدًا مع
تسليم موثوق للمنتجات الصناعية في جميع أنحاء العالم.
تجربة خالية من المخاطر لمدة 90 يومًا
ضمان لمدة سنتين
شحن وإرجاع مجانيان

REL72500
إذا كانت لديك أي أسئلة، فنحن نرحب باتصالك بنا في أي وقت. سنرد عليك في أقرب وقت ممكن، خلال 24 ساعة في أيام الأسبوع.
-
معلومات الشحن
استخدم هذا النص للإجابة على الأسئلة بأكبر قدر ممكن من التفصيل لعملائك.
-
دعم العملاء
استخدم هذا النص للإجابة على الأسئلة بأكبر قدر ممكن من التفصيل لعملائك.
-
الأسئلة الشائعة
استخدم هذا النص للإجابة على الأسئلة بأكبر قدر ممكن من التفصيل لعملائك.
-
اتصل بنا
استخدم هذا النص للإجابة على الأسئلة بأكبر قدر ممكن من التفصيل لعملائك.
الأسئلة الشائعة
يرجى قراءة صفحة الأسئلة الشائعة لمعرفة المزيد.
هل تقومون بتوريد منتجات أصلية؟
نحن نوفر منتجات الأتمتة الصناعية والكهربائية الأصلية من الشركات المصنعة الرائدة بما في ذلك سيمنز (Siemens) وإيه بي بي (ABB) وشنايدر إليكتريك (Schneider Electric) وفينكس كونتاكت (Phoenix Contact) وإيتون (Eaton). أصالة المنتجات وجودتها هي أولويتنا.
هل يمكنني طلب عرض أسعار؟
نعم. إذا لم يتم عرض الأسعار أو كنت بحاجة إلى عناصر متعددة، فما عليك سوى استخدام زر "طلب عرض أسعار" أو الاتصال بفريق المبيعات لدينا للحصول على عرض أسعار مخصص.
هل تشحنون دوليًا؟
نعم. نحن نوفر خدمة الشحن إلى جميع أنحاء العالم، ويمكننا توصيل المنتجات إلى العملاء في جميع أنحاء أوروبا والشرق الأوسط وآسيا ووجهات دولية أخرى.
هل يمكنك توفير قطع غيار قديمة أو يصعب العثور عليها؟
نعم. نحن متخصصون في توريد مكونات الأتمتة الصناعية التي توقف إنتاجها أو عفا عليها الزمن أو يصعب العثور عليها من خلال شبكة الموردين العالمية لدينا.
ما هي الصناعات التي تخدمونها؟
نحن ندعم العملاء في قطاعات الصناعة والنفط والغاز والطاقة والمرافق ومعالجة المياه والبنية التحتية والأتمتة الصناعية.