ATV71HU30Y
Schneider Electric Altivar 71 variable speed drive ATV71, 3kW, 690V, EMC filter-graphic terminal.
Show Specifications
Main Characteristics
| Lifecycle status | Discontinued by the manufacturer |
|---|---|
| Range of Product | Altivar 71 |
| Product or Component Type | Variable speed drive |
| Product Specific Application | Complex, high-power machines |
| Component name | ATV71 |
| Motor power kW | 2.2 kW, 3 phase 500 V; 3 kW, 3 phase 690 V |
| Maximum Horse Power Rating | 3 hp, 3 phase 575 V |
| Maximum motor cable length | 32.8 ft (10 m) shielded cable; 32.8 ft (10 m) unshielded cable |
| Power supply voltage | 500...690 V - 15...10 % |
| Phase | 3 phase |
| Line current | 4.4 A 600 V 3 phase / 3 hp; 5.2 A 500 V 3 phase 2.2 kW; 5.2 A 690 V 3 phase 3 kW |
| EMC filter | Integrated |
| Assembly style | With heat sink |
| Variant | Reinforced version |
| Prospective line Isc | 22 kA 3 phase |
| Nominal output current | 3.9 A 4 kHz 575 V 3 phase / 3 hp; 4.5 A 4 kHz 500 V 3 phase 2.2 kW; 4.5 A 4 kHz 690 V 3 phase 3 kW |
| Maximum transient current | 6.75 A 60 s 3 phase 2.2 kW |
| Output frequency | 0.1…500 Hz |
| Nominal switching frequency | 4 kHz |
| Switching frequency | 2.5...6 kHz adjustable; 4...6 kHz with derating factor |
| Asynchronous motor control profile | Sensorless flux vector control (SFVC) (voltage or current vector); ENA (Energy adaptation) system for unbalanced loads; Voltage/frequency ratio (2 or 5 points); Flux vector control (FVC) with sensor (current vector) |
| Type of polarization | No impedance Modbus |
Technical Data
| Product destination | Asynchronous motors; Synchronous motors |
|---|---|
| Power supply voltage limits | 425…759 V |
| Power supply frequency | 50...60 Hz - 5...5 % |
| Power supply frequency limits | 47.5...63 Hz |
| Speed range | 1…100 asynchronous motor in open-loop mode, without speed feedback; 1…1000 asynchronous motor in closed-loop mode with encoder feedback; 1…50 synchronous motor in open-loop mode, without speed feedback |
| Speed accuracy | +/- 0.01 % of nominal speed in closed-loop mode with encoder feedback 0.2 Tn to Tn; +/- 10 % of nominal slip without speed feedback 0.2 Tn to Tn |
| Torque accuracy | +/- 15 % in open-loop mode, without speed feedback; +/- 5 % in closed-loop mode with encoder feedback |
| Transient overtorque | 170 % +/- 10 % 60 s every 10 minutes; 220 % +/- 10 % 2 s |
| Braking torque | <= 150 % with braking or hoist resistor; 30 % without braking resistor |
| Synchronous motor control profile | Vector control without speed feedback |
| Regulation loop | Adjustable PI regulator |
| Motor slip compensation | Adjustable; Automatic whatever the load; Not available in voltage/frequency ratio (2 or 5 points); Suppressable |
| Diagnostic | 1 LED (red) for drive voltage |
| Output voltage | <= power supply voltage |
| Insulation | Electrical between power and control |
| Type of cable for mounting in an enclosure | With a NEMA Type1 kit 3 UL 508 cable 104 °F (40 °C), copper 75 °C / PVC; With an IP21 or an IP31 kit 3 IEC cable 104 °F (40 °C), copper 70 °C / PVC; Without mounting kit 1 IEC cable 113 °F (45 °C), copper 70 °C / PVC; Without mounting kit 1 IEC cable 113 °F (45 °C), copper 90 °C / XLPE/EPR |
| Electrical connection | Terminal 2.5 mm², 14 AWG AI1-/AI1+, AI2, AO1, R1A, R1B, R1C, R2A, R2B, LI1...LI6, PWR); Terminal 50 mm², 1/0 AWG L1/R, L2/S, L3/T, U/T1, V/T2, W/T3, PC/-, PO, PA/+, PA, PB) |
| Tightening torque | 5.3 lbf.in (0.6 N.m) AI1-/AI1+, AI2, AO1, R1A, R1B, R1C, R2A, R2B, LI1...LI6, PWR); 106.2 lbf.in (12 N.m), 102.2 lb.in L1/R, L2/S, L3/T, U/T1, V/T2, W/T3, PC/-, PO, PA/+, PA, PB) |
| Supply | Internal supply for reference potentiometer (1 to 10 kOhm) 10.5 V DC +/- 5 %, <10 mA overload and short-circuit protection; Internal supply 24 V DC 21…27 V), <200 mA overload and short-circuit protection |
| Analogue input number | 2 |
| Analogue input type | AI1-/Al1+ bipolar differential voltage +/- 10 V DC 24 V max 11 bits + sign; AI2 software-configurable current 0...20 mA 242 Ohm 11 bits; AI2 software-configurable voltage 0...10 V DC 24 V max 30000 Ohm 11 bits |
| Input sampling time | 2 ms +/- 0.5 ms AI1-/Al1+) - analog; 2 ms +/- 0.5 ms Al2) - analog; 2 ms +/- 0.5 ms LI1...LI5) - discrete; 2 ms +/- 0.5 ms LI6)if configured as logic input - discrete |
| Response time | <= 100 ms in STO (Safe Torque Off); AO1 2 ms +/- 0.5 ms analog; R1A, R1B, R1C 7 ms +/- 0.5 ms discrete; R2A, R2B 7 ms +/- 0.5 ms discrete |
| Absolute accuracy precision | +/- 0.6 % AI1-/Al1+) for a temperature variation 60 °C; +/- 0.6 % AI2) for a temperature variation 60 °C; +/- 1 % AO1) for a temperature variation 60 °C |
| Linearity error | +/- 0.15 % of maximum value AI1-/Al1+, AI2); +/- 0.2 % AO1) |
| Analogue output number | 1 |
| Analogue output type | AO1 software-configurable logic output 10 V 20 mA; AO1 software-configurable current 0...20 mA 500 Ohm 10 bits; AO1 software-configurable voltage 0...10 V DC 470 Ohm 10 bits |
| Discrete output number | 2 |
| Discrete output type | Configurable relay logic R1A, R1B, R1C) NO/NC - 100000 cycles; Configurable relay logic R2A, R2B) NO - 100000 cycles |
| Minimum switching current | 3 mA 24 V DC configurable relay logic |
| Maximum switching current | R1, R2 2 A 250 V AC inductive, cos phi = 0.4; R1, R2 2 A 30 V DC inductive, cos phi = 0.4; R1, R2 5 A 250 V AC resistive, cos phi = 1; R1, R2 5 A 30 V DC resistive, cos phi = 1 |
| Discrete input number | 7 |
| Discrete input type | LI1...LI5 programmable 24 V DC level 1 PLC 3500 Ohm; LI6 switch-configurable 24 V DC level 1 PLC 3500 Ohm; LI6 switch-configurable PTC probe 0…6 1500 Ohm; PWR safety input 24 V DC 1500 Ohm ISO 13849-1 level d |
| Discrete input logic | Negative logic (sink) LI1...LI5), > 16 V, 11 V; Negative logic (sink) LI6)if configured as logic input, > 16 V, 11 V |
| Acceleration and deceleration ramps | S, U or customized; Automatic adaptation of ramp if braking capacity exceeded, by using resistor; Linear adjustable separately from 0.01 to 9000 s |
| Braking to standstill | By DC injection |
| Protection type | Against exceeding limit speed drive; Against input phase loss drive; Break on the control circuit drive; Input phase breaks drive; Line supply overvoltage drive; Line supply undervoltage drive; Overcurrent between output phases and earth drive; Overheating protection drive; Overvoltages on the DC bus drive; Short-circuit between motor phases drive; Thermal protection drive; Motor phase break motor; Power removal motor; Thermal protection motor |
| Insulation resistance | > 1 mOhm 500 V DC for 1 minute to earth |
| Frequency resolution | Analog input 0.024/50 Hz; Display unit 0.1 Hz |
| Communication Port Protocol | CANopen; Modbus |
| Connector type | 1 RJ45 on front face)Modbus; 1 RJ45 on terminal)Modbus; Male SUB-D 9 on RJ45CANopen |
| Physical interface | 2-wire RS 485 Modbus |
| Transmission frame | RTU Modbus |
| Transmission rate | 4800 bps, 9600 bps, 19200 bps, 38.4 Kbps Modbus on terminal; 9600 bps, 19200 bps Modbus on front face; 20 kbps, 50 kbps, 125 kbps, 250 kbps, 500 kbps, 1 Mbps CANopen |
| Data format | 8 bits, 1 stop, even parity Modbus on front face; 8 bits, odd even or no configurable parity Modbus on terminal |
| Number of addresses | 1…127 CANopen; 1…247 Modbus |
| Method of access | Slave CANopen |
| Marking | CE |
| Operating position | Vertical +/- 10 degree |
| Height | 16.5 in (420 mm) |
| Depth | 9.3 in (236 mm) |
| Width | 9.4 in (240 mm) |
| Net Weight | 66.1 lb(US) (30 kg) |
| Option card | Communication card CC-Link; Controller inside programmable card; Communication card DeviceNet; Communication card EtherNet/IP; Communication card Fipio; I/O extension card; Communication card Interbus-S; Interface card for encoder; Communication card Modbus Plus; Communication card Modbus TCP; Communication card Modbus/Uni-Telway; Overhead crane card; Communication card Profibus DP; Communication card Profibus DP V1 |
Environment & Certifications
| Noise level | 59.9 dB 86/188/EEC |
|---|---|
| Dielectric strength | 3110 V DC between earth and power terminals; 5345 V DC between control and power terminals |
| Electromagnetic compatibility | 1.2/50 µs - 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5; Conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6; Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4; Electrostatic discharge immunity test level 3 conforming to IEC 61000-4-2; Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3; Voltage dips and interruptions immunity test conforming to IEC 61000-4-11 |
| Standards | IEC 61800-3 environments 1 category C3; IEC 61800-5-1; UL Type 1; IEC 60721-3-3 class 3C2; EN 55011 class A group 2; IEC 61800-3; IEC 61800-3 environments 2 category C3 |
| Product Certifications | NOM 117; CSA; UL; C-tick; GOST |
| Pollution degree | 2 IEC 61800-5-1; 3 UL 840 |
| IP degree of protection | IP20 on upper part without blanking plate on cover IEC 60529; IP20 on upper part without blanking plate on cover IEC 61800-5-1; IP21 IEC 60529; IP21 IEC 61800-5-1; IP41 on upper part IEC 60529; IP41 on upper part IEC 61800-5-1; IP54 on lower part IEC 60529; IP54 on lower part IEC 61800-5-1 |
| Vibration resistance | 1 gn (f= 13…200 Hz) conforming to IEC 60068-2-6; 1.5 mm peak to peak (f= 3…13 Hz) conforming to IEC 60068-2-6 |
| Shock resistance | 15 gn 11 ms IEC 60068-2-27 |
| Relative humidity | 5…95 % without condensation IEC 60068-2-3; 5…95 % without dripping water IEC 60068-2-3 |
| Ambient air temperature for operation | 14…122 °F (-10…50 °C) (without derating) |
| Ambient Air Temperature for Storage | -13…158 °F (-25…70 °C) |
| Operating altitude | <= 3280.84 ft (1000 m) without derating; 3280.84...7414.7 ft (1000...2260 m) with current derating 1 % per 100 m |
Packaging & Logistics
| Nbr. of units in pkg. | 1 |
|---|---|
| Package 1 Height | 10.2 in (26.0 cm) |
| Package 1 Width | 15.7 in (40.0 cm) |
| Package 1 Length | 23.6 in (60.0 cm) |
| Package weight(Lbs) | 68.3 lb(US) (31.0 kg) |
| GTIN | 3389119214803 |
Warranty
| Warranty (in months) | 18 |
|---|
Pairs well with
Worldwide delivery, dispatched from Erbil
Technical support before and after you order
Genuine parts from authorised manufacturers
Obsolete and hard-to-find items sourced

ATV71HU30Y
If you have any questions, you are always welcome to contact us. We'll get back to you as soon as possible, within 24 hours on weekdays.
-
Shipping
We ship worldwide from our warehouse in Erbil, Iraq, and deliver across Baghdad and all governorates. Stocked lines dispatch quickly; items sourced to order have their lead time confirmed in writing with your quote.
-
Technical support
Not sure which part you need, or whether an alternative is compatible? Send us the part number, the equipment it goes into, or a photo of the nameplate and our team will confirm the correct item before you order.
WhatsApp +964 781 287 9696 or sales@alnajahpower.com.
-
Pricing and quotes
Prices are not shown online because they depend on quantity, specification and current availability. Add the items you need to your quote list and send it — we reply within one business day with pricing and lead time.
-
Contact us
Alnajah Power
Makhmur Str. 83, Erbil 44020, IraqPhone / WhatsApp: +964 781 287 9696
sales@alnajahpower.comSaturday to Thursday, 09:00 – 18:00.
FAQs
Please read our FAQs page to find out more.
Do you supply genuine products?
We supply genuine industrial automation and electrical products from leading manufacturers including Siemens, ABB, Schneider Electric, Phoenix Contact, and Eaton. Product authenticity and quality are our priority.
Can I request a quotation?
Yes. If pricing is not displayed or you require multiple items, simply use the “Request a Quote” button or contact our sales team for a customized quotation.
Do you ship internationally?
Yes. We provide worldwide shipping and can deliver products to customers across Europe, the Middle East, Asia, and other international destinations.
Can you source obsolete or hard-to-find parts?
Yes. We specialize in sourcing discontinued, obsolete, and difficult-to-find industrial automation components through our global supplier network.
What industries do you serve?
We support customers in manufacturing, oil & gas, energy, utilities, water treatment, infrastructure, and industrial automation sectors.