LC1D115ALSE
Schneider Electric contactor, Tesys Deca Advanced, 3P(3NO), 75hp at 480V, 115A, 200-500V AC/DC coil, Everlink.
Show Specifications
Main Characteristics
| Range | TeSys Deca |
|---|---|
| Range of Product | TeSys Deca Advanced |
| Product or Component Type | Contactor |
| Contactor application | Motor control; Resistive load |
| Utilisation category | AC-3; AC-3e; AC-1; AC-4; DC-1; DC-3; DC-5 |
| Poles description | 3P |
| [Ue] rated operational voltage | Power circuit <= 1000 V AC 16.67...400 Hz; Power circuit <= 300 V DC |
| [Ie] rated operational current | 115 A (at <140 °F (60 °C)) at <= 440 V AC AC-3 for power circuit; 115 A (at <140 °F (60 °C)) at <= 440 V AC AC-3e for power circuit; 200 A (at <140 °F (60 °C)) at <= 440 V AC AC-1 for power circuit |
| [Uc] control circuit voltage | 200...500 V AC 50/60 Hz; 200...500 V DC |
Technical Data
| Motor power kW | 30 kW at 230 V AC 50/60 Hz (AC-3); 55 kW at 400 V AC 50/60 Hz (AC-3); 59 kW at 415 V AC 50/60 Hz (AC-3); 59 kW at 440 V AC 50/60 Hz (AC-3); 75 kW at 500 V AC 50/60 Hz (AC-3); 80 kW at 690 V AC 50/60 Hz (AC-3); 65 kW at 1000 V AC 50/60 Hz (AC-3); 30 kW at 230 V AC 50/60 Hz (AC-3e); 55 kW at 400 V AC 50/60 Hz (AC-3e); 59 kW at 415 V AC 50/60 Hz (AC-3e); 59 kW at 440 V AC 50/60 Hz (AC-3e); 75 kW at 500 V AC 50/60 Hz (AC-3e); 80 kW at 690 V AC 50/60 Hz (AC-3e); 65 kW at 1000 V AC 50/60 Hz (AC-3e); 30 kW at 230 V AC 50/60 Hz (AC-4); 55 kW at 400 V AC 50/60 Hz (AC-4); 55 kW at 440 V AC 50/60 Hz (AC-4); 63 kW at 500 V AC 50/60 Hz (AC-4); 65 kW at 690 V AC 50/60 Hz (AC-4); 50 kW at 1000 V AC 50/60 Hz (AC-4) |
|---|---|
| Maximum Horse Power Rating | 30 hp at 200/208 V 60 Hz; 40 hp at 230/240 V 60 Hz; 75 hp at 460/480 V 60 Hz; 100 hp at 575/600 V 60 Hz |
| Compatibility code | LC1D |
| Pole contact composition | 3 NO |
| Protective cover | With |
| [Ith] conventional free air thermal current | 200 A (at 140 °F (60 °C)) for power circuit |
| Irms rated making capacity | 1560 A at 440 V for power circuit conforming to IEC 60947; 140 A AC for signalling circuit conforming to IEC 60947-5-1; 250 A DC for signalling circuit conforming to IEC 60947-5-1 |
| Rated breaking capacity | 1100 A at 440 V for power circuit conforming to IEC 60947 |
| [Icw] rated short-time withstand current | 350 A 104 °F (40 °C) - 10 min for power circuit; 600 A 104 °F (40 °C) - 1 min for power circuit; 1280 A 104 °F (40 °C) - 10 s for power circuit; 1800 A 104 °F (40 °C) - 1 s for power circuit; 100 A - 1 s for signalling circuit; 120 A - 500 ms for signalling circuit; 140 A - 100 ms for signalling circuit |
| Associated fuse rating | 125 A aM at <= 440 V for power circuit; 100 A aM at <= 690 V for power circuit; 200 A gG at <= 690 V for power circuit; 10 A gG for signalling circuit; 0.5 A gG for control circuit |
| Average impedance | 0.45 mOhm - Ith 200 A 50 Hz for power circuit |
| Power dissipation per pole | 6 W AC-3; 6 W AC-3e; 22 W AC-1 |
| [Ui] rated insulation voltage | Power circuit 600 V CSA; Power circuit 600 V UL; Power circuit 1000 V IEC 60947-4-1; Signalling circuit 690 V IEC 60947-1; Signalling circuit 600 V CSA; Signalling circuit 600 V UL |
| Overvoltage category | III |
| Pollution degree | 3 |
| [Uimp] rated impulse withstand voltage | 8 kV IEC 60947 |
| Safety reliability level | B10d = 684932 cycles contactor with nominal load EN/ISO 13849-1; B10d = 10000000 cycles contactor with mechanical load EN/ISO 13849-1 |
| Mechanical durability | 8 Mcycles |
| Electrical durability | 1 Mcycles 115 A AC-3 <= 440 V; 1 Mcycles 115 A AC-3e <= 440 V; 0.5 Mcycles 200 A AC-1 <= 440 V |
| Control circuit type | AC 50/60 Hz; DC |
| Coil technology | Built-in bidirectional peak limiting diode suppressor |
| Control circuit voltage limits | 0.8 Uc Min...1.1 Uc Max (-40…140 °F (-40…60 °C)):operational AC/DC; 0.1 Uc Max (-40…140 °F (-40…60 °C)):drop-out AC/DC |
| Inrush power in VA | 170 VA (at 68 °F (20 °C)) |
| Inrush power in W | 120 W 68 °F (20 °C)) |
| Hold-in power consumption in VA | 16.5 VA (at 68 °F (20 °C)) |
| Hold-in power consumption in W | 5.1 W 68 °F (20 °C) |
| Heat dissipation | 3 W at 20 °C |
| Operating time | 10...80 ms opening; 20...90 ms closing |
| Maximum operating rate | 2400 cyc/h at 60 °C; 3600 cyc/h at Uc at 20 ºC |
| Connections - terminals | Power circuit: connector 1 0.02…0.2 in² (10…120 mm²) - cable stiffness: flexible without cable end; Power circuit: connector 2 0.02…0.08 in² (10…50 mm²) - cable stiffness: flexible without cable end; Power circuit: connector 1 0.02…0.2 in² (10…120 mm²) - cable stiffness: flexible with cable end; Power circuit: connector 2 0.02…0.08 in² (10…50 mm²) - cable stiffness: flexible with cable end; Power circuit: connector 1 0.02…0.2 in² (10…120 mm²) - cable stiffness: solid without cable end; Power circuit: connector 2 0.02…0.08 in² (10…50 mm²) - cable stiffness: solid without cable end; Control circuit: screw clamp terminals 1 0.002…0.006 in² (1…4 mm²) - cable stiffness: flexible with cable end; Control circuit: screw clamp terminals 2 0.002…0.004 in² (1…2.5 mm²) - cable stiffness: flexible with cable end; Control circuit: screw clamp terminals 1 0.002…0.006 in² (1…4 mm²) - cable stiffness: flexible without cable end; Control circuit: screw clamp terminals 2 0.002…0.006 in² (1…4 mm²) - cable stiffness: flexible without cable end; Control circuit: screw clamp terminals 1 0.002…0.006 in² (1…4 mm²) - cable stiffness: solid without cable end; Control circuit: screw clamp terminals 2 0.002…0.006 in² (1…4 mm²) - cable stiffness: solid without cable end |
| Tightening torque | Power circuit 106.2 lbf.in (12 N.m) connector hexagonal 0.2 in (4 mm); Control circuit 15.05 lbf.in (1.7 N.m) screw clamp terminals flat Ø 6 mm; Control circuit 15.05 lbf.in (1.7 N.m) screw clamp terminals Philips No 2; Control circuit 15.05 lbf.in (1.7 N.m) screw clamp terminals pozidriv No 2 |
| Auxiliary contact composition | 1 NO + 1 NC |
| Auxiliary contacts type | Mechanically linked 1 NO + 1 NC IEC 60947-5-1; Mirror contact 1 NC IEC 60947-4-1 |
| Signalling circuit frequency | 16.67...400 Hz |
| Minimum switching voltage | 17 V for signalling circuit |
| Minimum switching current | 5 mA for signalling circuit |
| Insulation resistance | > 10 MOhm for signalling circuit |
| Non-overlap time | 1.5 ms on de-energisation between NC and NO contact; 1.5 ms on energisation between NC and NO contact |
| Mounting Support | Plate |
Environment & Certifications
| Standards | EN/IEC 60947-4-1; EN/IEC 60947-5-1; UL 60947-4-1; UL 60947-5-1; CSA C22.2 No 60947-4-1; CSA C22.2 No 60947-5-1; JIS C8201-4-1; JIS C8201-5-1; GB/T 14048.4; GB/T 14048.5 |
|---|---|
| Product Certifications | CB Scheme; CCC; cULus; CE; UKCA; EU-RO-MR by DNV-GL |
| IP degree of protection | IP20 front face IEC 60529 |
| Protective treatment | NoneIEC 60068-2-30 |
| Climatic withstand | IACS E10 exposure to damp heat; IEC 60947-1 Annex Q category D exposure to damp heat |
| Permissible ambient air temperature around the device | -40…140 °F (-40…60 °C) operation; 140…158 °F (60…70 °C) with derating; -76…176 °F (-60…80 °C) storage |
| Operating altitude | 0...9842.52 ft (0...3000 m) without derating |
| Fire resistance | 1562 °F (850 °C) IEC 60695-2-11 |
| Mechanical robustness | Vibrations contactor open 2 Gn, 5...300 Hz) IEC 60068-2-6; Vibrations contactor closed 4 Gn, 5...300 Hz) IEC 60068-2-6; Shocks contactor open 10 Gn for 11 ms) IEC 60068-2-27; Shocks contactor closed 15 Gn for 11 ms) IEC 60068-2-27 |
| Height | 6.0 in (152 mm) |
| Width | 3.8 in (97 mm) |
| Depth | 6.1 in (155 mm) |
| Net Weight | 5.3 lb(US) (2.4 kg) |
Packaging & Logistics
| Nbr. of units in pkg. | 1 |
|---|---|
| Package 1 Height | 5.236 in (13.300 cm) |
| Package 1 Width | 7.244 in (18.400 cm) |
| Package 1 Length | 7.638 in (19.400 cm) |
| Package weight(Lbs) | 5.860 lb(US) (2.658 kg) |
| Number of Units in Package 2 | 4 |
| Package 2 Height | 11.811 in (30.000 cm) |
| Package 2 Width | 11.811 in (30.000 cm) |
| Package 2 Length | 15.748 in (40.000 cm) |
| Package 2 Weight | 24.460 lb(US) (11.095 kg) |
| Number of Units in Package 3 | 24 |
| Package 3 Height | 28.937 in (73.500 cm) |
| Package 3 Width | 23.622 in (60.000 cm) |
| Package 3 Length | 31.496 in (80.000 cm) |
| Package 3 Weight | 169.602 lb(US) (76.930 kg) |
| GTIN | 3606486976982 |
| Country of origin | CN |
Warranty
| Warranty (in months) | 18 |
|---|
Pairs well with
Worldwide delivery, dispatched from Erbil
Technical support before and after you order
Genuine parts from authorised manufacturers
Obsolete and hard-to-find items sourced

LC1D115ALSE
If you have any questions, you are always welcome to contact us. We'll get back to you as soon as possible, within 24 hours on weekdays.
-
Shipping
We ship worldwide from our warehouse in Erbil, Iraq, and deliver across Baghdad and all governorates. Stocked lines dispatch quickly; items sourced to order have their lead time confirmed in writing with your quote.
-
Technical support
Not sure which part you need, or whether an alternative is compatible? Send us the part number, the equipment it goes into, or a photo of the nameplate and our team will confirm the correct item before you order.
WhatsApp +964 781 287 9696 or sales@alnajahpower.com.
-
Pricing and quotes
Prices are not shown online because they depend on quantity, specification and current availability. Add the items you need to your quote list and send it — we reply within one business day with pricing and lead time.
-
Contact us
Alnajah Power
Makhmur Str. 83, Erbil 44020, IraqPhone / WhatsApp: +964 781 287 9696
sales@alnajahpower.comSaturday to Thursday, 09:00 – 18:00.
FAQs
Please read our FAQs page to find out more.
Do you supply genuine products?
We supply genuine industrial automation and electrical products from leading manufacturers including Siemens, ABB, Schneider Electric, Phoenix Contact, and Eaton. Product authenticity and quality are our priority.
Can I request a quotation?
Yes. If pricing is not displayed or you require multiple items, simply use the “Request a Quote” button or contact our sales team for a customized quotation.
Do you ship internationally?
Yes. We provide worldwide shipping and can deliver products to customers across Europe, the Middle East, Asia, and other international destinations.
Can you source obsolete or hard-to-find parts?
Yes. We specialize in sourcing discontinued, obsolete, and difficult-to-find industrial automation components through our global supplier network.
What industries do you serve?
We support customers in manufacturing, oil & gas, energy, utilities, water treatment, infrastructure, and industrial automation sectors.