LC1D956F7
Schneider Electric TeSys Deca Advanced TeSys Deca contactor , 3P(3 NO) , AC-3/AC-3e , <= 440V, 95 A , 110V AC 50/60 Hz coil.
Show Specifications
Main Characteristics
| Lifecycle status | Discontinued by the manufacturer |
|---|---|
| Range | TeSys |
| Range of Product | TeSys Deca Advanced |
| Product or Component Type | Contactor |
| Contactor application | Motor control; Resistive load |
| Utilisation category | AC-3; AC-3e; AC-1; AC-4 |
| Poles description | 3P |
| [Ue] rated operational voltage | Power circuit <= 1000 V AC 25...400 Hz |
| [Ie] rated operational current | 95 A (at <140 °F (60 °C)) at <= 440 V AC-3 for power circuit; 125 A (at <140 °F (60 °C)) at <= 1000 V AC-1 for power circuit; 95 A (at <140 °F (60 °C)) at <= 440 V AC-3e for power circuit |
| [Uc] control circuit voltage | 110 V AC 50/60 Hz |
Technical Data
| Motor power kW | 25 kW at 220/230 V AC 50/60 Hz (AC-3); 45 kW at 380/400 V AC 50/60 Hz (AC-3); 45 kW at 415/440 V AC 50/60 Hz (AC-3); 55 kW at 500 V AC 50/60 Hz (AC-3); 45 kW at 660/690 V AC 50/60 Hz (AC-3); 25 kW at 220/230 V AC 50/60 Hz (AC-3e); 45 kW at 380/400 V AC 50/60 Hz (AC-3e); 45 kW at 415/440 V AC 50/60 Hz (AC-3e); 55 kW at 500 V AC 50/60 Hz (AC-3e); 45 kW at 660/690 V AC 50/60 Hz (AC-3e); 15 kW at 400 V AC 50/60 Hz (AC-4) |
|---|---|
| Maximum Horse Power Rating | 7.5 hp at 120 V AC 60 Hz for 1 phase motors; 15 hp at 230/240 V AC 60 Hz for 1 phase motors; 30 hp at 200/208 V AC 60 Hz for 3 phase motors; 30 hp at 230/240 V AC 60 Hz for 3 phase motors; 60 hp at 460/480 V AC 60 Hz for 3 phase motors; 60 hp at 575/600 V AC 60 Hz for 3 phase motors |
| Compatibility code | LC1D |
| Pole contact composition | 3 NO |
| Protective cover | With |
| [Ith] conventional free air thermal current | 10 A (at 140 °F (60 °C)) for signalling circuit; 125 A (at 140 °F (60 °C)) for power circuit |
| Irms rated making capacity | 1100 A at 440 V AC for power circuit conforming to IEC 60947; 140 A AC for signalling circuit conforming to IEC 60947-5-1; 250 A DC for signalling circuit conforming to IEC 60947-5-1 |
| Rated breaking capacity | 1100 A at 440 V for power circuit conforming to IEC 60947 |
| [Icw] rated short-time withstand current | 1100 A 104 °F (40 °C) - 1 s for power circuit; 800 A 104 °F (40 °C) - 10 s for power circuit; 400 A 104 °F (40 °C) - 1 min for power circuit; 135 A 104 °F (40 °C) - 10 min for power circuit; 140 A - 100 ms for signalling circuit; 120 A - 500 ms for signalling circuit; 100 A - 1 s for signalling circuit |
| Associated fuse rating | 10 A gG for signalling circuit conforming to IEC 60947-5-1; 200 A gG at <= 690 V coordination type 1 for power circuit; 160 A gG at <= 690 V coordination type 2 for power circuit |
| Average impedance | 0.8 mOhm - Ith 125 A 50 Hz for power circuit |
| Power dissipation per pole | 12.5 W AC-1; 7.2 W AC-3; 7.2 W AC-3e |
| [Ui] rated insulation voltage | Power circuit 1000 V IEC 60947-4-1; Power circuit 600 V CSA; Power circuit 600 V UL; Signalling circuit 690 V IEC 60947-1; Signalling circuit 600 V CSA; Signalling circuit 600 V UL |
| Overvoltage category | III |
| Pollution degree | 3 |
| [Uimp] rated impulse withstand voltage | 8 kV IEC 60947 |
| Safety reliability level | B10d = 1.3 Mcycles contactor with nominal load EN/ISO 13849-1; B10d = 20 Mcycles contactor with mechanical load EN/ISO 13849-1 |
| Mechanical durability | 4 Mcycles |
| Electrical durability | 1.2 Mcycles 95 A AC-3; 1.3 Mcycles 125 A AC-1; 1.2 Mcycles 95 A AC-3e |
| Control circuit type | AC 50/60 Hz |
| Coil technology | Without built-in suppressor module |
| Control circuit voltage limits | 0.8...1.1 Uc (-40…131 °F (-40…55 °C)):operational AC 50 Hz; 0.85...1.1 Uc (-40…131 °F (-40…55 °C)):operational AC 60 Hz; 0.3...0.6 Uc (-40…158 °F (-40…70 °C)):drop-out AC 50/60 Hz; 1...1.1 Uc (131…158 °F (55…70 °C)):operational AC 50/60 Hz |
| Inrush power in VA | 245 VA 60 Hz cos phi 0.75 (at 68 °F (20 °C)); 245 VA 50 Hz cos phi 0.75 (at 68 °F (20 °C)) |
| Hold-in power consumption in VA | 26 VA 60 Hz cos phi 0.3 (at 68 °F (20 °C)); 26 VA 50 Hz cos phi 0.3 (at 68 °F (20 °C)) |
| Heat dissipation | 6…10 W at 50/60 Hz |
| Operating time | 20...35 ms closing; 6...20 ms opening |
| Maximum operating rate | 3600 cyc/h at 60 °C |
| Connections - terminals | Control circuit: lugs-ring terminals - external diameter: 0.3 in (8 mm); Power circuit: bars 1 - busbar cross section: 3 x 16 mm; Power circuit: lugs-ring terminals - external diameter: 0.7 in (17 mm) |
| Tightening torque | Control circuit 10.6 lbf.in (1.2 N.m) lugs-ring terminals flat Ø 6 mm M3.5; Control circuit 10.6 lbf.in (1.2 N.m) lugs-ring terminals Philips No 2 M3.5; Power circuit 44.3 lbf.in (5 N.m) lugs-ring terminals flat Ø 8 mm M6; Power circuit 44.3 lbf.in (5 N.m) lugs-ring terminals hexagonal 0.4 in (10 mm) M6; Power circuit 44.3 lbf.in (5 N.m) bars flat Ø 8 mm M6; Power circuit 44.3 lbf.in (5 N.m) bars hexagonal 0.4 in (10 mm) M6; Control circuit 10.6 lbf.in (1.2 N.m) screw clamp terminals pozidriv No 2 M3.5 |
| Auxiliary contact composition | 1 NO + 1 NC |
| Auxiliary contacts type | Mechanically linked 1 NO + 1 NC IEC 60947-5-1; Mirror contact 1 NC IEC 60947-4-1 |
| Signalling circuit frequency | 25...400 Hz |
| Minimum switching voltage | 17 V for signalling circuit |
| Minimum switching current | 5 mA for signalling circuit |
| Insulation resistance | > 10 MOhm for signalling circuit |
| Non-overlap time | 1.5 ms on de-energisation between NC and NO contact; 1.5 ms on energisation between NC and NO contact |
| Mounting Support | Plate; Rail |
Environment & Certifications
| Standards | EN 60947-4-1; EN 60947-5-1; IEC 60947-4-1; IEC 60947-5-1; CSA C22.2 No 14; UL 60947-4-1; IEC 60335-2-40:Annex JJ; UL 60335-2-40:Annex JJ; IEC 60335-1:Clause 30.2 |
|---|---|
| Product Certifications | CCC; UL; CB Scheme; CSA; CE; UKCA; Marine; EAC |
| IP degree of protection | IP20 front face IEC 60529 |
| Protective treatment | THIEC 60068-2-30 |
| Climatic withstand | IACS E10 exposure to damp heat |
| Permissible ambient air temperature around the device | -40…140 °F (-40…60 °C); 140…158 °F (60…70 °C) with derating |
| Operating altitude | 0...9842.52 ft (0...3000 m) |
| Fire resistance | 1562 °F (850 °C) IEC 60695-2-1 |
| Flame retardance | V1 conforming to UL 94 |
| Mechanical robustness | Vibrations contactor open 2 Gn, 5...300 Hz) ; Shocks contactor open 8 Gn for 11 ms) ; Vibrations contactor closed 3 Gn, 5...300 Hz) ; Shocks contactor closed 10 Gn for 11 ms) |
| Height | 5 in (127 mm) |
| Width | 3.3 in (85 mm) |
| Depth | 5.1 in (130 mm) |
| Net Weight | 3.55 lb(US) (1.61 kg) |
Packaging & Logistics
| Nbr. of units in pkg. | 1 |
|---|---|
| Package 1 Height | 6.1 in (15.5 cm) |
| Package 1 Width | 3.7 in (9.5 cm) |
| Package 1 Length | 5.3 in (13.5 cm) |
| Package weight(Lbs) | 3.5 lb(US) (1.6 kg) |
| GTIN | 3389110298338 |
| Country of origin | CZ |
Warranty
| Warranty (in months) | 18 |
|---|
Pairs well with
Worldwide delivery, dispatched from Erbil
Technical support before and after you order
Genuine parts from authorised manufacturers
Obsolete and hard-to-find items sourced

LC1D956F7
If you have any questions, you are always welcome to contact us. We'll get back to you as soon as possible, within 24 hours on weekdays.
-
Shipping
We ship worldwide from our warehouse in Erbil, Iraq, and deliver across Baghdad and all governorates. Stocked lines dispatch quickly; items sourced to order have their lead time confirmed in writing with your quote.
-
Technical support
Not sure which part you need, or whether an alternative is compatible? Send us the part number, the equipment it goes into, or a photo of the nameplate and our team will confirm the correct item before you order.
WhatsApp +964 781 287 9696 or sales@alnajahpower.com.
-
Pricing and quotes
Prices are not shown online because they depend on quantity, specification and current availability. Add the items you need to your quote list and send it — we reply within one business day with pricing and lead time.
-
Contact us
Alnajah Power
Makhmur Str. 83, Erbil 44020, IraqPhone / WhatsApp: +964 781 287 9696
sales@alnajahpower.comSaturday to Thursday, 09:00 – 18:00.
FAQs
Please read our FAQs page to find out more.
Do you supply genuine products?
We supply genuine industrial automation and electrical products from leading manufacturers including Siemens, ABB, Schneider Electric, Phoenix Contact, and Eaton. Product authenticity and quality are our priority.
Can I request a quotation?
Yes. If pricing is not displayed or you require multiple items, simply use the “Request a Quote” button or contact our sales team for a customized quotation.
Do you ship internationally?
Yes. We provide worldwide shipping and can deliver products to customers across Europe, the Middle East, Asia, and other international destinations.
Can you source obsolete or hard-to-find parts?
Yes. We specialize in sourcing discontinued, obsolete, and difficult-to-find industrial automation components through our global supplier network.
What industries do you serve?
We support customers in manufacturing, oil & gas, energy, utilities, water treatment, infrastructure, and industrial automation sectors.