LC2D126B7
Schneider Electric TeSys Deca reversing contactor, 3P(3 NO), AC-3, <= 440 V 12 A, 24 V AC coil.
Show Specifications
Main Characteristics
| Lifecycle status | Discontinued by the manufacturer |
|---|---|
| Range | TeSys |
| Product name | TeSys Deca |
| Product or Component Type | Reversing contactor |
| Contactor application | Resistive load; Motor control |
| Utilisation category | AC-3; AC-1 |
| Device presentation | Preassembled with reversing power busbar |
| Poles description | 3P |
| Power pole contact composition | 3 NO |
| [Ue] rated operational voltage | Power circuit <= 690 V AC 25...400 Hz; Power circuit <= 300 V DC |
| [Ie] rated operational current | 25 A (at <140 °F (60 °C)) at <= 440 V AC AC-1 for power circuit; 12 A (at <140 °F (60 °C)) at <= 440 V AC AC-3 for power circuit |
| Motor power kW | 3 kW at 220...230 V AC 50 Hz; 5.5 kW at 380...400 V AC 50 Hz; 5.5 kW at 415...440 V AC 50 Hz; 7.5 kW at 500 V AC 50 Hz; 7.5 kW at 660...690 V AC 50 Hz |
| Maximum Horse Power Rating | 1 hp at 115 V AC 60 Hz for 1 phase motors; 2 hp at 230/240 V AC 60 Hz for 1 phase motors; 3 hp at 200/208 V AC 60 Hz for 3 phase motors; 3 hp at 230/240 V AC 60 Hz for 3 phase motors; 7.5 hp at 460/480 V AC 60 Hz for 3 phase motors; 10 hp at 575/600 V AC 60 Hz for 3 phase motors |
| Control circuit type | AC 50/60 Hz |
| [Uc] control circuit voltage | 24 V AC 50/60 Hz |
| Auxiliary contact composition | 1 NO + 1 NC |
| [Uimp] rated impulse withstand voltage | 6 kV IEC 60947 |
| Overvoltage category | III |
| [Ith] conventional free air thermal current | 10 A (at 140 °F (60 °C)) for signalling circuit; 25 A (at 140 °F (60 °C)) for power circuit |
| Irms rated making capacity | 250 A at 440 V for power circuit conforming to IEC 60947; 140 A AC for signalling circuit conforming to IEC 60947-5-1; 250 A DC for signalling circuit conforming to IEC 60947-5-1 |
| Rated breaking capacity | 250 A at 440 V for power circuit conforming to IEC 60947 |
| [Icw] rated short-time withstand current | 30 A 104 °F (40 °C) - 10 min for power circuit; 61 A 104 °F (40 °C) - 1 min for power circuit; 105 A 104 °F (40 °C) - 10 s for power circuit; 210 A 104 °F (40 °C) - 1 s for power circuit; 100 A - 1 s for signalling circuit; 120 A - 500 ms for signalling circuit; 140 A - 100 ms for signalling circuit |
| Associated fuse rating | 10 A gG for signalling circuit conforming to IEC 60947-5-1; 40 A gG at <= 690 V coordination type 1 for power circuit; 25 A gG at <= 690 V coordination type 2 for power circuit |
| Average impedance | 2.5 mOhm - Ith 25 A 50 Hz for power circuit |
| [Ui] rated insulation voltage | Power circuit 690 V IEC 60947-4-1; Power circuit 600 V CSA; Power circuit 600 V UL; Signalling circuit 690 V IEC 60947-1; Signalling circuit 600 V CSA; Signalling circuit 600 V UL |
| Electrical durability | 2 Mcycles 12 A AC-3 <= 440 V; 0.8 Mcycles 25 A AC-1 <= 440 V |
| Power dissipation per pole | 1.56 W AC-1; 0.36 W AC-3 |
| Front cover | With |
| Interlocking type | Mechanical |
| Mounting Support | Plate; Rail |
| Standards | CSA C22.2 No 14; EN 60947-4-1; EN 60947-5-1; IEC 60947-4-1; IEC 60947-5-1; UL 508 |
| Product Certifications | DNV; CCC; UL; LROS (Lloyds register of shipping); CSA; RINA; GOST; GL; BV |
| Connections - terminals | Control circuit lugs-ring terminals 0.3 in (8 mm)) ; Power circuit lugs-ring terminals 0.3 in (8 mm)) |
| Tightening torque | Control circuit 15.05 lbf.in (1.7 N.m) lugs-ring terminals flat Ø 6 mm M3.5; Control circuit 15.05 lbf.in (1.7 N.m) lugs-ring terminals Philips No 2 M3.5; Power circuit 15.05 lbf.in (1.7 N.m) lugs-ring terminals flat Ø 8 mm M3.5; Power circuit 15.05 lbf.in (1.7 N.m) lugs-ring terminals Philips No 2 M3.5 |
| Operating time | 12...22 ms closing; 4...19 ms opening |
| Safety reliability level | B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1; B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1 |
| Mechanical durability | 15 Mcycles |
| Maximum operating rate | 3600 cyc/h 140 °F (60 °C) |
Technical Data
| Coil technology | Without built-in suppressor module |
|---|---|
| Control circuit voltage limits | 0.3...0.6 Uc (-40…158 °F (-40…70 °C)):drop-out AC 50/60 Hz; 0.8...1.1 Uc (-40…140 °F (-40…60 °C)):operational AC 50 Hz; 0.85...1.1 Uc (-40…140 °F (-40…60 °C)):operational AC 60 Hz; 1...1.1 Uc (140…158 °F (60…70 °C)):operational AC 50/60 Hz |
| Inrush power in VA | 70 VA 60 Hz cos phi 0.75 (at 68 °F (20 °C)); 70 VA 50 Hz cos phi 0.75 (at 68 °F (20 °C)) |
| Hold-in power consumption in VA | 7.5 VA 60 Hz cos phi 0.3 (at 68 °F (20 °C)); 7 VA 50 Hz cos phi 0.3 (at 68 °F (20 °C)) |
| Heat dissipation | 2…3 W 50/60 Hz |
| Auxiliary contacts type | Mechanically linked 1 NO + 1 NC IEC 60947-5-1; Mirror contact 1 NC IEC 60947-4-1 |
| Signalling circuit frequency | 25...400 Hz |
| Minimum switching current | 5 mA for signalling circuit |
| Minimum switching voltage | 17 V for signalling circuit |
| Non-overlap time | 1.5 ms on de-energisation between NC and NO contact; 1.5 ms on energisation between NC and NO contact |
| Insulation resistance | > 10 MOhm for signalling circuit |
Environment & Certifications
| IP degree of protection | IP20 front face IEC 60529 |
|---|---|
| Climatic withstand | IACS E10; IEC 60947-1 Annex Q category D |
| Protective treatment | TH IEC 60068-2-30 |
| Pollution degree | 3 |
| Ambient air temperature for operation | -40…140 °F (-40…60 °C); 140…158 °F (60…70 °C) with derating |
| Ambient Air Temperature for Storage | -76…176 °F (-60…80 °C) |
| Operating altitude | 0...9842.52 ft (0...3000 m) |
| Fire resistance | 1562 °F (850 °C) IEC 60695-2-1 |
| Flame retardance | V1 conforming to UL 94 |
| Mechanical robustness | Vibrations contactor open2 Gn, 5...300 Hz; Vibrations contactor closed4 Gn, 5...300 Hz; Shocks contactor open10 Gn for 11 ms; Shocks contactor closed15 Gn for 11 ms |
| Height | 3.03 in (77 mm) |
| Width | 3.5 in (90 mm) |
| Depth | 3.4 in (86 mm) |
| Net Weight | 1.537 lb(US) (0.697 kg) |
Packaging & Logistics
| Nbr. of units in pkg. | 1 |
|---|---|
| Package 1 Height | 3.7 in (9.4 cm) |
| Package 1 Width | 4.5 in (11.4 cm) |
| Package 1 Length | 4.3 in (11 cm) |
| Package weight(Lbs) | 25.7 oz (730 g) |
| GTIN | 3389110661743 |
| Country of origin | FR |
Warranty
| Warranty (in months) | 18 |
|---|
Pairs well with
Worldwide delivery, dispatched from Erbil
Technical support before and after you order
Genuine parts from authorised manufacturers
Obsolete and hard-to-find items sourced
LC2D126B7
If you have any questions, you are always welcome to contact us. We'll get back to you as soon as possible, within 24 hours on weekdays.
-
Shipping
We ship worldwide from our warehouse in Erbil, Iraq, and deliver across Baghdad and all governorates. Stocked lines dispatch quickly; items sourced to order have their lead time confirmed in writing with your quote.
-
Technical support
Not sure which part you need, or whether an alternative is compatible? Send us the part number, the equipment it goes into, or a photo of the nameplate and our team will confirm the correct item before you order.
WhatsApp +964 781 287 9696 or sales@alnajahpower.com.
-
Pricing and quotes
Prices are not shown online because they depend on quantity, specification and current availability. Add the items you need to your quote list and send it — we reply within one business day with pricing and lead time.
-
Contact us
Alnajah Power
Makhmur Str. 83, Erbil 44020, IraqPhone / WhatsApp: +964 781 287 9696
sales@alnajahpower.comSaturday to Thursday, 09:00 – 18:00.
FAQs
Please read our FAQs page to find out more.
Do you supply genuine products?
We supply genuine industrial automation and electrical products from leading manufacturers including Siemens, ABB, Schneider Electric, Phoenix Contact, and Eaton. Product authenticity and quality are our priority.
Can I request a quotation?
Yes. If pricing is not displayed or you require multiple items, simply use the “Request a Quote” button or contact our sales team for a customized quotation.
Do you ship internationally?
Yes. We provide worldwide shipping and can deliver products to customers across Europe, the Middle East, Asia, and other international destinations.
Can you source obsolete or hard-to-find parts?
Yes. We specialize in sourcing discontinued, obsolete, and difficult-to-find industrial automation components through our global supplier network.
What industries do you serve?
We support customers in manufacturing, oil & gas, energy, utilities, water treatment, infrastructure, and industrial automation sectors.