REL50493
Schneider Electric protection and control relay, PowerLogic P5T30 24-48V 6CT 2Io 1VT 10DI-8DO.
Show Specifications
Main Characteristics
| Range of product | PowerLogic P5 |
|---|---|
| Product or component type | Protection and control relay |
| Relay application | Transformer differential |
| Product reference | P5T30-AADB-JAAAA-BAEA |
| Mounting case size | 30TE |
| Device mounting | Flush |
| Mounting support | Rack |
| Mounting mode | Withdrawable |
| Power supply | 24...48 V DC |
| Measuring inputs | : 1/5 A CT phase current 6; : 1/5 A CT residual current 2; : VT voltage 1 |
| Number of sensors | 0 temperature sensor(s) |
| Number of Digital Inputs (DI) | 10 |
| Number of analogue inputs | 0 |
| Number of Digital Outputs (DO) | 1 watchdog; 7 digital |
| Number of analogue outputs | 0 |
| Communication ports | USB port 2 front |
| Cybersecurity | Port hardening; Firmware signature; Client IP address filter; Secured communication with assciated tools; Role-based access control; Security policy management; Security log; LDAP; RADIUS based user authentication; IEC 62443-4-2 SL1 |
| Protection functions | Two-winding transformer differential 87T; Overfluxing (V/Hz) 24; Phase overcurrent 50/51; Earth fault overcurrent 50N/51N; Directional earth fault 67N; Thermal overload for transformer 49F; Thermostat / buchholz 26/63; Restricted earth fault 64REF; Current unbalance 46BC; Broken conductor 46BC; H2 detection 68H2; Breaker failure 50BF; Negative sequence overcurrent 46; Earth fault overvoltage 59N; Lockout relay 86; CT supervision 60; Programmable stages 99; Programmable curve; Programmable logic |
| Arc flash protection | No |
| Measurement functions | Current 3-phase; Current zero sequence; Current positive sequence; Current negative sequence; Current ratio of negative and positive; Current phasor diagram view; Current 2nd, 15th harmonics with THD; Voltage per phase; Voltage residual; Frequency |
| Control functions | Switchgear control and monitoring; Programmable switchgear interlocking; Local/remote control; 2 function keys |
| Controllable switchgear devices | 6 controlled + 2 monitored objects |
| Number of setting groups | 4 |
| Monitoring functions | Trip circuit supervision 74; Circuit breaker monitoring; Relay self-monitoring |
| Logs and records | Event recording; Disturbance recording; Tripping context; Relay maintenance |
| Connections - terminals | Pin removable (digital input/output); Ring lugs (current transformer); Ring lugs (voltage transformer); Screw (connector) |
Technical Data
| Software name | EcoStruxure Power Device: virtual simulation test; ESetup Easergy Pro |
|---|---|
| Display type | Colour LCD 480 x 272 pixels |
| Number of key | 7 customizable |
| Local signalling | 10 x LED tri-colour programmable; 4 x LED red programmable |
| Height | 176 mm |
| Width | 152 mm |
| Depth | 219 mm |
| Net weight | 3.5 kg maximum |
Environment & Certifications
| Climatic withstand | Exposure to dry heat conforming to IEC 60068-2-2; Exposure to cold conforming to IEC 60068-2-1; Exposure to damp heat in service conforming to IEC 60068-2-30; Exposure to damp heat in service conforming to IEC 60068-2-78; Temperature variation conforming to IEC 60068-2-14; Salt mist conforming to IEC 60068-2-52; Influence of corrosion/gas test 2 conforming to IEC 60068-2-60; Stationary use at weather protected locations conforming to IEC 60721-3-3 |
|---|---|
| Mechanical robustness | Vibrations conforming to GOST 17516.1; Vibrations conforming to IACS E10; Shocks (level: class II) conforming to IEC 60255-21-2; Seismic tests (level: class II) conforming to IEC 60255-21-3; Bumps (level: class II) conforming to IEC 60255-21-2; Vibrations (level: class II) conforming to IEC 60255-21-1 |
| Electromagnetic compatibility | Emission tests conforming to IACS E10; Emission tests class A conforming to CISPR 11; Emission tests class A conforming to CISPR 32; EMC immunity level 4 conforming to IEC 61000-4-2; EMC immunity level 3 conforming to IEC 61000-4-3; EMC immunity level 4 conforming to IEC 61000-4-4; EMC immunity level 4 conforming to IEC 61000-4-5; EMC immunity level 3 conforming to IEC 61000-4-6; EMC immunity level 5 conforming to IEC 61000-4-8; EMC immunity conforming to IACS E10; EMC immunity level 5 conforming to IEC 61000-4-10; EMC immunity conforming to IEC 61000-4-12; EMC immunity level 4 conforming to IEC 61000-4-16; EMC immunity level 3 conforming to IEC 61000-4-18; EMC immunity conforming to ANSI C37.90.1; EMC immunity conforming to ANSI C37.90.2; EMC immunity class 4 conforming to ANSI C37.90.3; EMC immunity conforming to GOST 30804.4.12; EMC immunity conforming to GOST 32137; EMC immunity conforming to GOST 30804.4.3 |
| Ambient air temperature for operation | -40…85 °C ( 16 h ) ; -40…70 °C ( 96 h ) |
| IP degree of protection | IP54 conforming to IEC 60529 |
| Maximum operating altitude | 2000 m |
| Protective treatment | Conformal coating conforming to IEC 60068-2-52:Kb/1; Conformal coating conforming to IEC 60068-2-60:Ke; Conformal coating conforming to IEC 60721-3-3:3C2 |
| Relative humidity | 0…95 % at 40 °C, without condensation, 56 days; 93…95 % at 25…55 °C, 6 cycles, 12 + 12 hours |
Packaging & Logistics
| Number of Units in Package 1 | 1 |
|---|---|
| Package 1 Height | 30 cm |
| Package 1 Width | 30 cm |
| Package 1 Length | 40 cm |
| Package 1 Weight | 4.441 kg |
Warranty
| Warranty (in months) | 24 |
|---|
Pairs well with
Worldwide delivery, dispatched from Erbil
Technical support before and after you order
Genuine parts from authorised manufacturers
Obsolete and hard-to-find items sourced

REL50493
If you have any questions, you are always welcome to contact us. We'll get back to you as soon as possible, within 24 hours on weekdays.
-
Shipping
We ship worldwide from our warehouse in Erbil, Iraq, and deliver across Baghdad and all governorates. Stocked lines dispatch quickly; items sourced to order have their lead time confirmed in writing with your quote.
-
Technical support
Not sure which part you need, or whether an alternative is compatible? Send us the part number, the equipment it goes into, or a photo of the nameplate and our team will confirm the correct item before you order.
WhatsApp +964 781 287 9696 or sales@alnajahpower.com.
-
Pricing and quotes
Prices are not shown online because they depend on quantity, specification and current availability. Add the items you need to your quote list and send it — we reply within one business day with pricing and lead time.
-
Contact us
Alnajah Power
Makhmur Str. 83, Erbil 44020, IraqPhone / WhatsApp: +964 781 287 9696
sales@alnajahpower.comSaturday to Thursday, 09:00 – 18:00.
FAQs
Please read our FAQs page to find out more.
Do you supply genuine products?
We supply genuine industrial automation and electrical products from leading manufacturers including Siemens, ABB, Schneider Electric, Phoenix Contact, and Eaton. Product authenticity and quality are our priority.
Can I request a quotation?
Yes. If pricing is not displayed or you require multiple items, simply use the “Request a Quote” button or contact our sales team for a customized quotation.
Do you ship internationally?
Yes. We provide worldwide shipping and can deliver products to customers across Europe, the Middle East, Asia, and other international destinations.
Can you source obsolete or hard-to-find parts?
Yes. We specialize in sourcing discontinued, obsolete, and difficult-to-find industrial automation components through our global supplier network.
What industries do you serve?
We support customers in manufacturing, oil & gas, energy, utilities, water treatment, infrastructure, and industrial automation sectors.