Schneider Electric analog input module, Modicon Premium, 4 high level inputs, 16 bits conversion, 660mA at 5VDC.
Show Specifications
Main Characteristics
| Lifecycle status | Discontinued by the manufacturer |
|---|---|
| Range of Product | Modicon Premium Automation platform |
| Product or Component Type | Analog input module |
| Input level | Low level |
| Analogue input number | 4 |
| Analogue input type | Current 4...20 mA; Voltage +/- 10 V; Voltage 0...10 V; Voltage 0...5 V; Voltage 1...5 V; Thermocouple thermocouple B; Thermocouple thermocouple E; Thermocouple thermocouple J; Thermocouple thermocouple K; Thermocouple thermocouple L; Thermocouple thermocouple N; Thermocouple thermocouple R; Thermocouple thermocouple S; Thermocouple thermocouple T; Thermocouple thermocouple U; Resistor 0...3850 Ohm; Resistor 0...400 Ohm; Temperature probe Ni 1000 2 wires; Temperature probe Ni 1000 4 wires; Temperature probe Pt 100 2 wires; Temperature probe Pt 100 4 wires; Temperature probe Pt 1000 2 wires; Temperature probe Pt 1000 4 wires; Voltage - 13...63 mV; Voltage +/- 5 V |
| Analog/digital conversion | 16 bits |
Technical Data
| Nominal read cycle time | 550 ms |
|---|---|
| Measurement error | 0.13 % of full scale 0...400 Ohm 25 °C; 0.16 % of full scale 0...10 V 25 °C; 0.19 % of full scale - 13...63 mV 25 °C; 0.22 % of full scale 0...3850 Ohm 25 °C; 0.22 % of full scale 0...5 V 25 °C; 0.27 % of full scale +/- 10 V 25 °C; 0.27 % of full scale +/- 5 V 25 °C; 0.27 % of full scale 0...400 Ohm 0...60 °C; 0.27 % of full scale 1...5 V 25 °C; 0.39 % of full scale 0...10 V 0...60 °C; 0.44 % of full scale - 13...63 mV 0...60 °C; 0.45 % of full scale 0...5 V 0...60 °C; 0.45 % of full scale 4...20 mA 25 °C; 0.48 % of full scale 0...3850 Ohm 0...60 °C; 0.5 % of full scale +/- 10 V 0...60 °C; 0.5 % of full scale +/- 5 V 0...60 °C; 0.56 % of full scale 1...5 V 0...60 °C; 0.86 % of full scale 4...20 mA 0...60 °C; 1.5 °C thermocouple B external 25 °C; 1.5 °C thermocouple E external 25 °C; 1.5 °C thermocouple T external 25 °C; 1.5 °C thermocouple U external 25 °C; 1.8 °C thermocouple J external 25 °C; 10.5 °C thermocouple K internal 0...60 °C; 11 °C thermocouple R internal 0...60 °C; 12 °C thermocouple S internal 0...60 °C; 2 °C thermocouple L external 25 °C; 2 °C thermocouple N external 25 °C; 2.3 °C thermocouple K external 25 °C; 3.1 °C thermocouple U external 0...60 °C; 3.2 °C thermocouple E external 0...60 °C; 3.2 °C thermocouple R external 25 °C; 3.2 °C thermocouple T external 0...60 °C; 3.4 °C thermocouple S external 25 °C; 3.5 °C thermocouple B external 0...60 °C; 3.5 °C thermocouple B internal 25 °C; 3.8 °C thermocouple J external 0...60 °C; 4.1 °C thermocouple L external 0...60 °C; 4.3 °C thermocouple N external 0...60 °C; 4.7 °C thermocouple K external 0...60 °C; 5.4 °C thermocouple U internal 25 °C; 6 °C thermocouple N internal 25 °C; 6 °C thermocouple R internal 25 °C; 6.1 °C thermocouple E internal 25 °C; 6.6 °C thermocouple S internal 25 °C; 6.6 °C thermocouple T internal 25 °C; 7.3 °C thermocouple J internal 25 °C; 7.3 °C thermocouple U internal 0...60 °C; 7.5 °C thermocouple L internal 25 °C; 7.7 °C thermocouple R external 0...60 °C; 7.8 °C thermocouple K internal 25 °C; 8.1 °C thermocouple B internal 0...60 °C; 8.1 °C thermocouple E internal 0...60 °C; 8.5 °C thermocouple S external 0...60 °C; 8.7 °C thermocouple N internal 0...60 °C; 8.8 °C thermocouple T internal 0...60 °C; 9.5 °C thermocouple J internal 0...60 °C; 9.8 °C thermocouple L internal 0...60 °C; 1 °C Ni 1000 25 °C; 1.2 °C Pt 100 25 °C; 2 °C Ni 1000 0...60 °C; 2.4 °C Pt 100 0...60 °C; 2.5 °C Pt 1000 25 °C; 5 °C Pt 1000 0...60 °C |
| Isolation between channels and bus | 1780 Vrms |
| Isolation between channels and ground | 1780 Vrms |
| Isolation between channels | 2830 Vrms |
| Common mode between channels | 415 V AC or 200 V DC |
| Common mode between channels and earth | 240 V AC or 110 V DC |
| Input overvoltage protection | -15…15 V at state 0 250 Ohm; -30…30 V at state 1 250 Ohm |
| Electrical connection | Screw terminal block |
| Overcurrent | -30…30 mA at state 1 250 kOhm |
| Marking | CE |
| Current consumption | 660 mA 5 V DC |
| Module format | Standard |
| Net Weight | 0.71 lb(US) (0.32 kg) |
Environment & Certifications
| Standards | DIN 43760; IEC 584; IEC 751; DIN 43710; NFC 42-330; IEC 1131 |
|---|---|
| Product Certifications | DNV; BV; ABS; RMRS; RINA; GL; LR |
| Ambient Air Temperature for Operation | 32…140 °F (0…60 °C) |
| Ambient Air Temperature for Storage | -13…158 °F (-25…70 °C) |
| Relative Humidity | 10…95 % without condensation for operation; 5…95 % without condensation for storage |
| Operating altitude | 0...6561.68 ft (0...2000 m) |
| Protective treatment | TC |
| IP Degree of Protection | IP20 |
| Pollution degree | 2 |
Packaging & Logistics
| Nbr. of units in pkg. | 1 |
|---|---|
| Package 1 Height | 2.2 in (5.5 cm) |
| Package 1 Width | 7.09 in (18.0 cm) |
| Package 1 Length | 10.2 in (26.0 cm) |
| Package weight(Lbs) | 16.05 oz (455.0 g) |
| GTIN | 3389110756951 |
| Country of origin | FR |
Warranty
| Warranty (in months) | 18 |
|---|
Pairs well with
Worldwide delivery, dispatched from Erbil
Technical support before and after you order
Genuine parts from authorised manufacturers
Obsolete and hard-to-find items sourced

TSXAEY414
If you have any questions, you are always welcome to contact us. We'll get back to you as soon as possible, within 24 hours on weekdays.
-
Shipping
We ship worldwide from our warehouse in Erbil, Iraq, and deliver across Baghdad and all governorates. Stocked lines dispatch quickly; items sourced to order have their lead time confirmed in writing with your quote.
-
Technical support
Not sure which part you need, or whether an alternative is compatible? Send us the part number, the equipment it goes into, or a photo of the nameplate and our team will confirm the correct item before you order.
WhatsApp +964 781 287 9696 or sales@alnajahpower.com.
-
Pricing and quotes
Prices are not shown online because they depend on quantity, specification and current availability. Add the items you need to your quote list and send it — we reply within one business day with pricing and lead time.
-
Contact us
Alnajah Power
Makhmur Str. 83, Erbil 44020, IraqPhone / WhatsApp: +964 781 287 9696
sales@alnajahpower.comSaturday to Thursday, 09:00 – 18:00.
FAQs
Please read our FAQs page to find out more.
Do you supply genuine products?
We supply genuine industrial automation and electrical products from leading manufacturers including Siemens, ABB, Schneider Electric, Phoenix Contact, and Eaton. Product authenticity and quality are our priority.
Can I request a quotation?
Yes. If pricing is not displayed or you require multiple items, simply use the “Request a Quote” button or contact our sales team for a customized quotation.
Do you ship internationally?
Yes. We provide worldwide shipping and can deliver products to customers across Europe, the Middle East, Asia, and other international destinations.
Can you source obsolete or hard-to-find parts?
Yes. We specialize in sourcing discontinued, obsolete, and difficult-to-find industrial automation components through our global supplier network.
What industries do you serve?
We support customers in manufacturing, oil & gas, energy, utilities, water treatment, infrastructure, and industrial automation sectors.